Utilizziamo cookie per assicurarti una migliore esperienza sul sito. Utilizziamo cookie di parti terze per inviarti messaggi promozionali personalizzati. Per maggiori informazioni sui cookie e sulla loro disabilitazione consulta la Cookie Policy. If you continue browsing you consent to the use of cookies.
 

LIGHTENED CLS 100mm - EI 120

Fire retrofit of existing CLS walls

 

Reference standard: EN 1364-1:2015
Fire resistance: EI 120
Flame impingement: Fire exposure on the protected side
Wall stratigraphy: Wall with a minimum thickness of 100 mm in single-chamber, lightened, exposed cls concrete blocks
Environmental certification: Indoor Air Comfort Gold®6.0 dated 02/2017 – EPD in accordance with ISO 14025 and EN 15804
Protective system: Amotherm Brick WB – water-based, single-component paint
Consumption: 1.20 kg/m2
Technical reference document: Classification Report I.G. 374541/4058 FR
Technical file: Technical report I.G. n. 387592- F.T. n.04/2021
Height in the field of direct application: 4 m
Height extension: Not allowed
Extension in width: Admitted
Surface preparation: Amotherm Primer WB at a rate of 0.15 kg/m2

 
 
amotherm - foto2 amotherm - foto1